Main technical parameter
(1) Company code (2) Motor protector (3) Current sampling type (active type) (4) Design serial number (specification code) (5) Current regulation method: potentiometer quantitative setting (static) (6) Output method: None: one NC 1Z: one NO and one NC 2H: two NO L: One NC connect ammeter(internal resistance is 156Ω, full scale 1mA) Y: Wiring typeApplication
Working power | AC380V、AC220V 50Hz;The allowable voltage fluctuation range is (85%-110%) Ue |
Adjustment method | Online current adjustment by potentiometer |
Output control contact | a group of NC contact(Customizable according to customer requirements) |
Reset mode | Power off reset |
Contact capacity | AC-12,Ue:AC380V, Ie:3A |
Mechanical life | 1×105 time |
Electrical life | 1×104 time |
Installation | Device type |
Rated working current | ||||
Model | Setting current range (A) | Suitable motor power (kW) | Minimum sampling current(A) | Use DC meter ratio |
AS-22C/□ | 1~5 | 0.5~2.5 | 0.5 | 1mA/5A |
AS-22C/□ | 5~50 | 2.5~25 | 2 | 1mA/50A |
AS-22C/□ | 20~100 | 10~50 | 5 | 1mA/100A |
AS-22C/□ | 30~160 | 15~80 | 10 | 1mA/200A |
AS-22C/□ | 40~200 | 20~100 | 10 | 1mA/200A |
Overload Action Time Characteristics | ||||
Trip level | Different current multiples and action time PT | |||
1.05Ie | 1.2Ie | 1.5Ie | 7.2Ie | |
2 | Tp:no action within 2 hours | Tp:action within 2 hours | Tp≤1min | Tp≤4s |
5 | Tp≤2min | 0.5s<Tp≤5s | ||
10(A) | Tp≤4min | 2s<Tp≤10s | ||
15 | Tp≤6min | 4s<Tp≤15s | ||
20 | Tp≤8min | 6s<Tp≤20s | ||
25 | Tp≤10min | 8s<Tp≤25s | ||
30 | Tp≤12min | 9s<Tp≤30s |
Model Number Structure
Features
●Conform to GB/T14048.4 and many other national or industry standards. |
●Three-phase electronic type, the trip level is 30. |
●Possess current phase failure and overload protection functions, sensitive phase failure protection, reliable operation, and anti-interference ability Strong, set current value and overload delay are continuously adjustable; and have good inverse time characteristics and other advantages point. |
●The main circuit adopts the core-through current sampling method, combined with advanced electronic (integrated circuit) circuits. |
●Installation method: socket type, Din-rail type installation. |
Wiring diagram
Outline and installation dimensions
AS-22C (30-160A、40-200A)
AS-22C (1-5A、5-50A、20-100A)
Application circuit example
Diagram (1) The working voltage of the protector is 380V; the AC contactor is 380V